Customer called about water source heat pump not heating at times. Master service technician checked operation of system and cleaned water strainer. Strainer was found partially clogged. Recommend building maintenance should try to boost pressures and flow to this floor. Changed aux temperature sensor setting from 35 to 40 degrees. Problem resolved.