No cool. 2005 Amana split gas for mobile home. Found condenser fan motor out on thermal overload. Cooled motor off and started motor again. Checked amps, motor was pulling 2.2 amps rated for 1.8. Recommened to customer to replace motor but also discussed replacement options due to age of equipment and r22 phase out. Customer just wanted motor repalced today. Replaced motor and tested operation. No other issues found at this time. Refrigerant pressures seemed off, but that is due to high heat load in the house.