Christian V.

Christian V. Job Checkin

Arrived on site and traced conduit. Found switch junction box for sign. Switch for power to sign was in off position. Turned power and tested sign. Full power restored to sign. Turn on timer for sign in mechanical room inside store. Informed customer that power was restored to sign. All systems functioning properly. Job fully complete.


Christian V.

Christian V. Job Checkin

During install Ambient found that they could not pull wire from the existing Junction box. There are several circuits in box that need to be re pulled. Need to install underground pull box to bring up to code, this will also allow us to install water proof wire nuts. Re pulling all existing circuits and reconnecting, including adding additional circuit for lift station. Installed underground junction/pull box approx 5 feet from air compressor. Removed old wire and pulled new wire into new junction box. Removed wire at Sewage pump control panel and ran new wire to underground junction box. Made all proper connections at breaker panels and in junction box. Tested all connections. Power to pump, light pole and air compressor. Pumps operational. All connections secured and tight. Could not locate box for sign pole and power was not restored to it. Need to return to trace conduit and repair sign tomorrow. No issues to report. Customer satisfied with todays service. Collected payment a


Christian V.

Christian V. Job Checkin

Ambient is to supply and install (2) New pumps for the lift station at Chevron. ALso adding New control panels, floats and surge protectors. Ambient will install an additional electrical circuit from electrical panel to the lift station to give all pumps dedicated circuits. Day one- Removed old pumps and floats. Installed new floats and ran float wire to panel. Installed check valve on piping system at outlet. Installed new pumps and ran wire to panel. All wiring ran to panel for pump system and labeled. Pumps and floats installed. Day Two- Installed and wired new control panel to pumps and floats. Installed surge protectors on system. Unable to pull new wire due to illegal junction box in ground in irrigation control box. Robert to give estimate to customer to replace with legal junction box and new wire for dedicated circuit. Filled pit and tested pumps. Pumps operating correctly, power to box and surge protectors. No issues. Pumps firing. Bathrooms up and running in building


Larry G.

Larry G. Job Checkin

Sewer injector pumps connectors, repair the temporary, get the gas station, restrooms, up and running. We will return and probably get estimates on installing new connector controls


Michael A.

Michael A. Job Checkin

Arrived on site and checked in with staff. Installed part into blue bunny case found temping correctly but excessive build up of ice. Heater strip tests fine. Ambient edge did not diagnose this system. We cannot hold any warranty on parts or this piece of equipment. All work is complete. Nobody available on site to collect payment.


Christopher W.

Christopher W. Job Checkin

Supply and install new Indoor Head unit. Tech notes from site visit - Existing unit was found to have Large amounts of exposed insulation and wiring harness chewed. Highly recommend replacement of system as entire harness would need to be replaced, sensors, motor, eev, and boards as a start


Brian A.

Brian A. Job Checkin

As per mfg tech, system was addressed wrong. Went thru all 5 indoor units, thermostats and condenser and corrected addresses. Turned system on and checked operation. Indoor units 1-4 are working and cooling correctly. Indoor unit 5 is not getting any refrigerant. Due to extensive damage to wiring and control boards, recommended replacing indoor unit 5. Will work with office to have quote sent over.


Michael A.

Michael A. Job Checkin

Arrived on site and called Todd. Explained where key to site was located. Entered building using key to find Mitsubishi system with 5 heads. 4 turned on to different rooms but #1 turned off. Used thermostat to set system to cooling. System fan ran but no cooling. All other heads operating correctly. Opened system by removing power and cover and found system is coated inside with mouse excrement and urine. Large amounts of exposed insulation and wiring harness chewed. Highly recommend replacement of system as entire harness would need to be replaced, sensors, motor, eev, and boards as a start. Would cost more to repair system than it would for replacement. Not including labor to completely dissemble unit for chemical cleaning. Spoke to Todd about problems and system replacement option. Todd was interested in replacement of mini split head number 1. Will provide quote. Customer is portal to portal. Will bill for all travel as well. Attached all pics to job notes. Cannot guarantee functio


Larry G.

Larry G. Job Checkin

Arrived on site March 15, 2020 to Home Depot job the Home Depot side of this job canceled due to homeowners floor being on level. Reconnected customers stove screwed in the gas supply line and sprayed soap on the valve in line to verify no leaks, every burner lighted immediately reconnected customers refrigerator water supply line. Tested refrigerator to see if water was working water worked no leaks customer happy.


Larry G.

Larry G. Job Checkin

Arrived on site March 14, 2020 to Home Depot disconnect job. Disconnected the water supply line to refrigerator and disconnect the gas supply line to the stove floor guy was not ready for the toilet and we will disconnect and reconnect the toilet on our trip back.


Larry G.

Larry G. Job Checkin

Arrived on site March 14, 2020 to Home Depot disconnect job. Disconnected customers water supply line to the refrigerator and disconnected the gas to the stove. Check the gas supply line fittings and gas valve for leaks no leaks. We will have to disconnect and reconnect customers toilet on next trip customer only had one restroom and we worked it out with the flooring guy that it won’t take much time at all. Got the 110 form signed and the 113 form.