On arrival found thermostat in off position and service disconn3ct for outdoor unit in off position. Turned thermostat to Cool and applied power to outdoor unit. Noted that contactor is pulled in but nothing is running. Removed power and checked components. Found that condenser fan motor is burnt out and capacitor is wired incorrectly. Capacitor is wired so all power for compressor and fan is routed thru fan motor. Corrected wiring of capacitor and tested compressor. Compressor appears to be undamaged. Customer was also concerned about some wires that were sticking up thru the grill from the newly replaced fan motor. Explained that those wires are to change the rotation of the motor depending on what the unit requires. Wires are 240 volts and should not be left exposed for safety reasons. Explained that when I replace the motor the wires will be secured safely below the grill. Customer approved quote to replace fan motor, installed new universal motor and matching capacitor, explaining