8021 W. Gulf to Lake Hwy
Crystal River , FL 34429
352 795 2665

Job Locations
for san antonio, fl


Map of San Antonio FL
Cliff P.

Cliff P.


Job Checkin

Checked over the system to find everything to be working as designed. 53 percent humidity. 77 degree return air with. 55 degree supply air temperature. 56 degree wetbulb. 125/316 psi 12 degree Superheat. 8 degree Subcooling. 55 degree suction line temperature. 92 degree liquid line temperature. Sealed the air handler around the return and resealed around the supply. The system cooled down 3 degrees while checking it's operation.