Found protective foam in condensing coil housing that was being knocked around by the fan blade. Removed the foam and took out a dirty filter. Checked the capacitor, which was in the acceptable range of variance. Condensing fan motor is pulling 1.3/1.5 amps and compressor is pulling 8.8/13.1 amps. Temperature split, pressures, superheat, subcool, and static pressures are all good. System had a dirty condensing coil with slightly high head pressure. Recommend scheduling a checkup to optimize system performance and reduce risks of unit not working properly. Unit is cooling, running, and draining fine.