1. Furnish and install new cartridge at master bath shower valve. 2. Observed in crawlspace where the cold water supply line to the master bath lavatory faucet was freezing. No observable damage to the tubing at this time. Crawlspace air vent located approximately 5 feet to the right and a combination of needed additional insulation to block off airflow to the left to affect this tubing was the source. Installed a piece of insulation at a 90° angle to the left of the air vent to block off this flow of air and noted an immediate termination of cold air in the tubing area. 3. Noted a small drip at same lavatory faucet parentheses next to shower stall parentheses while repairing the shower valve. Quoted a task for repair vs. replacement of this faucet. Enrolled in the Value Maintenance Plan for one year. Two year labor and material warranty on Shower valve repair. No warranty on insulation work in an attempt to prevent tubing from possibly freezing. Paid by check.