Chris  M.

Chris M.


Job Checkin

Chris M came out due to no heat. Performed diagnostic. Found thermostat had no power at all to it. Went down into basement to furnace. Found furnace had no power to it. Went into garage where breaker panel was and found breaker had tripped. Performed further investigation of why furnace tripped breaker. Found a very dirty filter that got sucked into the furnace cabinet. Recommend replacing filters every 30 days. Filter size is 20x25x1. Found induction fan motor has plastic housing and has a start to a crack in it. The induction fan motor is rated for 1.7 amps and actual amps is 2.8 amps which is over amping. This is more than likely the main reasoning for the breaker to trip. Found hot surface igniter is very white which is early warning signs of failure. Found burner assembly is very dirty which is burning the fuel dirty and not at a clean rate. Found blower cabinet is very dirty and is recommended to be pulled and cleaned. Gave customer options. Got permission to perform work. Went t