Furnace clean and tune. Cycled system. Checked heat exchanger. Found all chambers are very rusted and corroded. No visible cracks found with camera. Checked, removed, and cleaned burners and flame sensor. Burners were corroded and rusted. Igniter is worn, but ok at this time. Igniter is very worn and it has deep etches. Found water leaks from ventor motor. Ventor motor bearings are worn and damaged. Checked gas pressures. Preformed combustion test and found elevated levels of XS air in exhaust. Traces to no CO found in airstream. Found large amount of condensate in transition assembly. Tried to clear water out of transition. I was unable to clear it out. Drain lines were clear. Found evidence that the secondary heat exchanger is clogging. Average life expectancy for this unit is 14 years. This unit is well past that time period. System is very worn and damaged, due to age, condition, and cost of repair, second opinion is recommended. System is operating safety at this time, but failure