Responded to a no-cool call on a Carrier Infinity system. Diagnosed a failed dual run capacitor and a clogged condensate drain line. Replaced the capacitor with a US-made Turbo 200 and cleared the drain line using nitrogen. Verified proper amperage draw on the compressor and fan motor. System is now cooling efficiently at 54 degrees supply temperature.