Job Checkin

AC Diagnostic System: Cottage # Burl M# 187BNA036000DDAA S# 3515E21813 Refrigerant Type R410A Metering Device-TXV SP/HP- 120/306 SLT/LLT- 54/87 VSAT/LSAT- 41/97 SH/SC- 13/10 Outdoor Entering Air Temperature Notes: Found blowout valve closed and water had filled up the drain pan. This was causing the float switch to trip and causing the unit to short cycle. I vacuumed out the water from the pan and opened up the blowout valve. Un8t is back up and running at this time.