30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for cleveland, tx


Map of Cleveland TX
Casey L.

Casey L.


Job Checkin

System- Rockwell/Poe Approx Age of System: Refrigerant Type- R410a Metering Device- TXV SP/HP: 120/330 SLT/LLT: 50/100 VSAT/LSAT-41/ 103 Superheat/Subcool-9/3 Outdoor Entering Air Temp- Outdoor Fan FLA- 0.61 Compressor RLA/LRA- 9.77 Contactor Voltage-242/26 Capacitor Rating-40.57/5.27 Indoor Return Dry Bulb Temp- 70 Return Wet Bulb Temp-56 Supply Temp-52 Temperature Difference-18 Required Difference-16 Filter Sizes – 20x25x4 Changed Filters – Yes Blew out drain line: Yes Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- System- Pearson/Burl Approx Age of System: Refrigerant Type- R410a Metering Device- TXV SP/HP: 116/334 SLT/LLT: 57/93 VSAT/LSAT- 39/103 Superheat/Subcool-18/10 Outdoor Entering Air Temp- Outdoor Fan FLA- 0.61 Compressor RLA/LRA-9.71 Contactor Voltage-241/27 Capacitor Rating-45.46/5.33 Indoor Return Dry Bulb Temp-69 Return Wet Bulb Temp-58 Supply Temp-51 Temperature Difference-18 Required