System-right side Approx Age of System: Refrigerant Type- R410a Metering Device- TXV SP/HP: 127/278 SLT/LLT: 61/83 VSAT/LSAT- 44/90 Superheat/subcool- 15/7 Outdoor Entering Air Temp-84 Outdoor Fan FLA-.9 Compressor RLA/LRA-10.3/100 Contactor Voltage-245/26 Capacitor Rating-45/5 actual 45/5 Indoor Return Dry Bulb Temp-75 Supply Temp-55 Temperature Difference-20 Required Difference-15-20 Blower FLA-3.8 Filter Sizes – 24x24x1,12x12x1,12x24x1 Changed Filters – N customer just changed Blew out drain line: Y Notes- Next Scheduled Tune up Date: --------------------------------------- System- left side Approx Age of System: Refrigerant Type- R410a Metering Device- TXV SP/HP: 124/291 SLT/LLT: 5/81 VSAT/LSAT- 43/94 Superheat/Subcool- 13/12 Outdoor Entering Air Temp-83 Outdoor Fan FLA-.7 Compressor RLA/LRA- 6.5/60 Contactor Voltage-246/26 Capacitor Rating-40/5 actual 40/5 Indoor Return Dry Bulb Temp-73 Supply Temp- 56 Temperature Difference-17 Required Difference-15-20