System- Approx Age of System: Refrigerant Type- R22 Metering Device- TXV SP/HP: 62/200 SLT/LLT: 45/88 VSAT/LSAT- 37/101 Superheat/Subcool- 9/13 Outdoor Entering Air Temp-80 Outdoor Fan FLA- 1.1 Compressor RLA/LRA- 14.2/ 144 Contactor Voltage- 244/25 Capacitor Rating- 55.20/6.98 Indoor Return Dry Bulb Temp- 69 Return Wet Bulb Temp- 58 Supply Temp- 50 Temperature Difference- 19 Required Difference- 16-20 Blower FLA- 5.6 Filter Sizes – 20x25x4 Changed Filters – N (customer will) Blew out drain line: Y Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. Condenser coil is clogged with debris. Condenser LRA is over rating. Contactor is humming, pitted and burnt. Condenser capacitor is bad rated 60/7.5mfd. All ot