30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for cypress, tx


Map of Cypress TX
Jeremy D.

Jeremy D.


Job Checkin

System- Upstairs Approx Age of System: 7yrs Refrigerant Type-R410a Metering Device-TXV SP/HP: 121/315 SLT/LLT: 58/86 VSAT/LSAT- 41/98 Superheat/Subcool- 17/12 Outdoor Entering Air Temp-86 Outdoor Fan FLA- 1.3 Compressor RLA/LRA- 8.6/84 Contactor Voltage-240/25 Capacitor Rating-36.46/4.43 Indoor Return Dry Bulb Temp- 75 Return Wet Bulb Temp- 60 Supply Temp- 56 Temperature Difference- 19 Required Difference- 16-20 Blower FLA-5.3 Filter Sizes – 12x36x1 Changed Filters – Acceptable Blew out drain line: N (no blowout valve) Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. Unit has no gas sediment. Gas flex connector is improperly installed. Condenser capacitor is bad rated for 45/5mfd. Condenser LRA is over rating of 77a. Unit has no overflow protection. All other components showed no visible issues at this time. Recommend capacitor-(to ensure operation), gas sediment