Diagnostic Follow Up Needed Warranty Capacitor Replacement Upstairs On arrival blower motor was operational. Checked filters. Filters are dirty. Checked safety switches. Unit has no overflow protection. Gas flex connector is improperly installed (pipe sealant in flared fittings). Checked condenser. Fan motor was operational. Compressor was not. Checked condenser electrical. Found bad capacitor rated for 40/5mfd and operating at 0/4.88mfd. Downstairs On arrival blower motor was operational. Checked filters. Filters are dirty. Checked safety switches. Unit has no overflow protection. Gas flex connector is improperly installed (pipe sealant in flared fittings). Checked condenser. Fan motor was operational. Compressor was not. Checked condenser electrical. Found bad capacitor rated for 45/5mfd and operating at 36.34/4.93mfd. Checked operating temperatures and pressures (see photos).