System- Single Approx Age of System: 5 Refrigerant Type- R410a Metering Device- TXV SP/HP: 118/288 SLT/LLT: 56/84 VSAT/LSAT- 40/92 Superheat/Subcool- 16/8 Outdoor Entering Air Temp- 79 Outdoor Fan FLA- 1.1 RLA/LRA- 10.5/130.6 (109) Contactor Voltage- 243.4 Capacitor Rating- 45/10 Indoor Return Dry Bulb Temp- 74 Return Wet Bulb Temp-64 Supply Temp- 55 Temperature Difference- 19 Required Difference- 18 Blower FLA- 5.1 Filter Sizes – 20x25x4 Changed Filters – Y Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Performed cooling tuneup. System was operational upon arrival. Compressor is over amping on startup. Scheduled next tune up date: 12/01 9-11