System- upstairs Approx Age of System: 16 Refrigerant Type- R22 Metering Device- TXV SP/HP: 73/212 SLT/LLT: 57/90 VSAT/LSAT- 43/105 Superheat/Subcool- 14/14 Outdoor Entering Air Temp- 87 Outdoor Fan FLA- 0.6 Compressor RLA/LRA- 7.8/64.7 (63) Contactor Voltage- 243 Capacitor Rating- 35/5 Indoor Return Dry Bulb Temp- 74 Return Wet Bulb Temp-64 Supply Temp- 60 Temperature Difference- 14 Required Difference- 17 Blower FLA- 4.6 Filter Sizes – 16x25x1 (2) Changed Filters – N Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Performed cooling tuneup. System was operational upon arrival. Compressor is over amping on startup. Condenser coil is deteriorating. R22 system - replacement was recommended. System- Downstairs Approx Age of System: 16 Refrigerant Type- R22 Metering Device- TXV SP/HP: 68/213 SLT/LLT: 47/95 VSAT/LSAT- 39/106 Superheat/Subcool- 8/12 Outdoor Entering Air Temp- 87 Outdoor