System-ds Approx Age of System: coil 2 condenser 3 Refrigerant Type- R410a Metering Device- TXV SP/HP: 129/291 SLT/LLT: 53/88 VSAT/LSAT- 45/94 Superheat/Subcool- 10/7 Outdoor Entering Air Temp-86 Outdoor Fan FLA- 1.1 Compressor RLA/LRA-12.3/117 (rated 109) Contactor Voltage- 243 Capacitor Rating-45/10 actual 45/9.8 Indoor Return Dry Bulb Temp-72 Return Wet Bulb Temp- 64 Supply Temp- 54 Temperature Difference-18 Required Difference-15-20 Blower FLA- 4.9 Filter Sizes – 20x25x4 Changed Filters – N Customer just changed Blew out drain line: N No blow out valves Returned tstat to original settings: Y/ Unit operational; prior to leaving: Y/ Notes- Scheduled next tune up date: System- up Approx Age of System: 4 Refrigerant Type- R410a Metering Device- TXV SP/HP: 121/293 SLT/LLT: 68/92 VSAT/LSAT- 42/94 Superheat/Subcool-21/5 Outdoor Entering Air Temp-86 Outdoor Fan FLA- .8 Compressor RLA/LRA-8.7/94 Contactor Voltage-244 Capacitor Rating-45/5