System- downstairs Approx Age of System: 11 Refrigerant Type- R410a Metering Device- TXV SP/HP: 128/299 SLT/LLT: 59/94 VSAT/LSAT- 44/95 Superheat/Subcool-16/6 Outdoor Entering Air Temp-86 Outdoor Fan FLA- .9 Compressor RLA/LRA-7.1/52 Contactor Voltage-240 Capacitor Rating- turbo Indoor Return Dry Bulb Temp-72 Return Wet Bulb Temp- 64 Supply Temp- 54 Temperature Difference-18 Required Difference-15-20 Blower FLA- 1.6 Filter Sizes – 20x25x1 Changed Filters – N customer will Blew out drain line: N no access Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Scheduled next tune up date: System- upstairs Approx Age of System: 11 Refrigerant Type- R410a Metering Device- TXV SP/HP: 133/309 SLT/LLT: 61/97 VSAT/LSAT- 46/96 Superheat/Subcool- 20/6 Outdoor Entering Air Temp-86 Outdoor Fan FLA- 1 Compressor RLA/LRA-7/47 Contactor Voltage-239 Capacitor Rating-Turbo Indoor Return Dry Bulb Temp-74 Return Wet Bulb Te