Job Checkin

AC Diagnostic System:York front part of store Refrigerant Type R22 Metering Device-TXV Pressures before repair SP/HP95.8/392.8 SLT/LLT58.7/135.9 VSAT/LSAT56.7/152.4 SH/SC2/16.5 Pressures after repair SP/HP78/230.9 SLT/LLT77.3/89.9 VSAT/LSAT55.7/102.1 SH/SC21.6/13. Outdoor Entering Air Temperature 88 Filter Size(s)18x24x2(4) Returned tstat to original settings: Y(75) Unit operational; prior to leaving: Y Notes: Upon arrival checked in with Mark and located unit which controls the front part of the store. Manager explained it was blowing air but it wasn’t cold. Went to outdoor package unit and found a trip on high head pressure. Reset system and made the call for cooling, after 5 minute delay one compressor came on and only one fan motor came on the other one was seized and not spinning. Tried to force it to spin but failed. Since the second fan motor doesn’t kick on the compressor head pressure gets too high and shuts down to protect the compressor. Took video of the unit reac