30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for houston, tx


Map of Houston TX
Henry M.

Henry M.


Job Checkin

AC Diagnostic System:1st/2nd floor Refrigerant Type R410A Metering Device-TXV SP/HP144.4/353.9 SLT/LLT72.8/99.8 VSAT/LSAT50.9/107.8 SH/SC22.6/8 Outdoor Entering Air Temperature 90 Filter Size(s)20x25x4(2) Returned tstat to original settings: Y(didn’t touch) Unit operational; prior to leaving: Y Notes: Upon arrival Mrs. Livermore said she heard noise coming from the drain line for the 1st and 2nd floor. And also saw small amount of water in the emergency drain pan. Found that the noise is from when only one thermostat is calling for cooling and the blower speed slows down and it’s the noise of the water hitting the ptrap. Also found the water was from small amount of air spilling from the seams and creating condensation from meeting with attic air. Explained that I did not have metal/foil tape since it was all used yesterday so had to tape up with duct tape, did not apply duct sealant so we could apply metal tape to the seams to keep all cold air in and keep it from mixing with