System- Downstairs Approx Age of System: 2yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 117/314 SLT/LLT: 56/83 VSAT/LSAT- 39/99 Superheat/Subcool- 16/15 Outdoor Entering Air Temp-82 Outdoor Fan FLA- .7 Compressor RLA/LRA- 12.0/124 Contactor Voltage- 245/26 Capacitor Rating- 69.90/5.01 Indoor Return Dry Bulb Temp- 74 Return Wet Bulb Temp- 58 Supply Temp-52 Temperature Difference- 22 Required Difference- 16-20 Filter Sizes – 20x25x1 Changed Filters – Y (customer supplied) Blew out drain line: N (no blowout valve) Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. All other components showed no visible issues at this time. Recommend compressor saver-(to reduce amp and extend equipment life), blowout valve-(to service primary drain line). System- Upstairs Approx Age of System: 2yrs