System- Approx Age of System: 1yr Refrigerant Type- R410a Metering Device- TXV SP/HP: 147/335 SLT/LLT: 57/98 VSAT/LSAT- 51/103 Superheat/Subcool- 6/5 Outdoor Entering Air Temp- 91 Outdoor Fan FLA- .5 Compressor RLA/LRA- 7.8/82 Contactor Voltage- 243/25 Capacitor Rating- 44.32/4.87 Indoor Return Dry Bulb Temp- 83 Return Wet Bulb Temp- 61 Supply Temp- 68 Temperature Difference- 20 Required Difference- 16-20 Blower FLA-7.8 Filter Sizes – 20x25 Changed Filters – acceptable Blew out drain line: Y Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. All other components showed no visible issues at this time. Recommend compressor saver-(to reduce amp and extend equipment life).