30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for katy, tx


Map of Katy TX
Casey L.

Casey L.


Job Checkin

System: RTU 1 Approx. Age of System: Combustible Gas Leak Detection Pipe and fittings leak-free: yes Valves and orifices leak-free: yes Carbon Monoxide Testing Walk-around CO: pass/0 ppm Airside CO: pass or fail/return 0 ppm supply 0 ppm Flue gas CO: pass or fail/22 ppm Ignition and Combustion Delayed ignition: no Flame disturbance: no Flame discoloration: no Motor Amperages and Capacitors Blower motor FLA: 1.70 Induced draft/combustion blower motor FLA: 0.31 Capacitor(s): pass or fail/mfd Temperature Rise Rated: 30-60 Actual: 41 Static Pressures Blower speed/cfm: RP 0.46 /SP 0.18 TESP: Safety Controls Primary limit test: pass Filter sizes: Changed filters: yes or no Scheduled next tune up date: Notes: ________________________________________ System: RTU 4 Approx. Age of System: Combustible Gas Leak Detection Pipe and fittings leak-free: yes Valves and orifices leak-free: yes Carbon Monoxide Testing Walk-around CO: pass or fail/0 ppm Airside CO: pass/r