Unit: RTU 10 Replaced the low ambient pressure switch on the high pressure side of the line set. Tested to make sure the fan would kick on after 450 psi and cut out at 250 psi. Low ambient switch is operating as it should at this time. Power has been restored to the unit after repair. Unit has been returned to operational state.