System- Downstairs Approx Age of System: 3 years Refrigerant Type- R410a Metering Device- TXV SP/HP: 102/242 SLT/LLT:41/72 VSAT/LSAT-33/81 Superheat/Subcool-8/9 Outdoor Entering Air Temp- 73 Outdoor Fan FLA- 1.13 Compressor RLA/LRA- 10.69/152.7 Contactor Voltage- 243/24 Capacitor Rating- 68.18/7.28 Indoor Return Dry Bulb Temp- 71 Supply Temp- 52 Temperature Difference- 19 Required Difference- 16 Filter Sizes – 20x30x1,12x24x1 Changed Filters – No. filters are clean Blew out drain line: Yes Notes- Found starting amperage exceeds the manufacturer spec. We currently have a starting amperage of 152.7 and the unit is rated for 135. I recommend adding start capacitor to assist in reducing the starting amperage and help extend the life of the compressor. . . . . . . . . . System- Upstairs Approx Age of System: 3 years Refrigerant Type- R410a Metering Device- TXV SP/HP: 118/245 SLT/LLT: 52/76 VSAT/LSAT-40/82 Superheat/Subcool- 12/8 Outdoor Entering Air Temp- 73 Outdoor