Casey L.

Casey L.


Job Checkin

System- RTU 5 Approx Age of System: Refrigerant Type- R410a Metering Device- TXV Outdoor Fan FLA- 1.67/1.69 Compressor RLA-5.25/5.31 Contactor Voltage-486/26 Capacitor Rating-9.62/9.51 Indoor Return Dry Bulb Temp-71 Supply Temp-52 Temperature Difference-19 Required Difference-16 Blower FLA- 3.76 Filter Sizes – 18x18x2 (6) Changed Filters – Yes Blew out drain line: No Returned tstat to original settings: Yes Unit operational; prior to leaving: Yes Notes- Scheduled next tune up date: System- RTU2 Approx Age of System: 3 years Refrigerant Type- R410a Metering Device- TXV Outdoor Fan FLA- 1.67/1.66 Compressor RLA-5.46/5.39 Contactor Voltage-482/26 Capacitor Rating-9.92/9.86 Indoor Return Dry Bulb Temp-74 Supply Temp-56 Temperature Difference-18 Required Difference-16 Blower FLA- 3.78 Filter Sizes – 18x18x2 (6) Changed Filters – Yes Blew out drain line: No Returned tstat to original settings: Yes Unit operational; prior to leaving: Yes N