System-Main Approx Age of System: 11 Refrigerant Type- R410a Metering Device- TXV SP/HP:149/342 SLT/LLT:57/97 VSAT/LSAT-46/106 Superheat/Subcool-11/9 Outdoor Entering Air Temp-90 Outdoor Fan FLA- 1.8 Compressor RLA/LRA-14.9/100 Contactor Voltage-28/220 Indoor Return Dry Bulb Temp-73 Return Wet Bulb Temp-64 Supply Temp-53 Temperature Difference-20 Required Difference-16-22 Blower FLA-5.8 Filter Sizes – 20x25x4 Changed Filters – Y (Customer supplied) Blew out drain line: N(no blow out valve) Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- system is cooling great, system is 11 yrs old and would definitely recommend saving up to replace system with new more efficient system being them life span is between 8-12 yrs, Scheduled next tune up date: