Job Checkin

System-Main Approx Age of System: 7 Refrigerant Type- R410a Metering Device- TXV SP/HP:114.9/328.5 SLT/LLT:49.4/92.5 VSAT/LSAT-38.4/102.3 Superheat/Subcool-11.1/9.9 Outdoor Entering Air Temp-85 Outdoor Fan FLA- R1.2 A .9 Compressor RLA/LRA-R21.8/117 A12.1/130.8 Contactor Voltage-248/26 Capacitor Rating-70/7.5 A64.04/4.6 Indoor Return Dry Bulb Temp-70.9 Return Wet Bulb Temp-61.7 Supply Temp- 52.8 Temperature Difference-18.1 Required Difference-15-21 Blower FLA- 7.2 Filter Sizes – 20x25x1 12x24x1 customer will change Changed Filters – N Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Arrived on site, met with customer. System was operational upon arrival. Performed ac tuneup, found no overflow protection system, and inrush current over specifications. Recommended overflow protection system, compressor saver, and air scrubber. Customers will look over quotes and let the office know if they decide to