System- single Approx Age of System: 1 Refrigerant Type- R410a Metering Device- TXV SP/HP: 117/237 SLT/LLT: 52/76 VSAT/LSAT- 39/80 Superheat/Subcool- 13/4 Outdoor Entering Air Temp- 66 Outdoor Fan FLA- 1.2 Compressor RLA/LRA- 9.9/119 Contactor Voltage- 246.0 Capacitor Rating- 70/10 Indoor Return Dry Bulb Temp- 67 Return Wet Bulb Temp- 59 Supply Temp- 51 Temperature Difference- 16 Required Difference- Filter Sizes – (Did not go inside) Changed Filters – N Blew out drain line: N Notes- performed ac tuneup. System was operational upon arrival. Found compressor over amping on startup. Found gas flex line installed incorrectly. Found no condensation protection on the system. Found organic growth on the supply plenum. Recommendations attached. Scheduled next tune up date: 10/28 8-10