Jacob C.

Jacob C.


Job Checkin

System-main Approx Age of System: 4 Refrigerant Type- R410a Metering Device- TXV SP/HP:103/271 SLT/LLT:75/87 VSAT/LSAT- 32/88 Superheat/Subcool-42/1.7 Outdoor Entering Air Temp-82 Outdoor Fan FLA- 1.0 Compressor RLA/LRA- 6.3/116 Contactor Voltage-243/26 Capacitor Rating-43/4.6 Indoor Return Dry Bulb Temp-78 Return Wet Bulb Temp-68 Supply Temp-59 Temperature Difference-19 Required Difference-16-24 Blower FLA- 3.7 Filter Sizes – 12x12x1 20x30x1 Changed Filters – Y ( only the 12x12 customer supplied ) Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Organic growth spotted in supply plenum, recommend an air scrubber to kill off romantic growth, help prevent further buildup, as well as increase air quality. Refrigerant Charge was low compared to Readings from last visit a couple weeks ago, system has service warranty still so topped off unit, added a pound and a half. Scheduled next tune up date: We