System- upstairs Approx Age of System: 5 Refrigerant Type- R410a Metering Device- TXV SP/HP: 131/293 SLT/LLT: 66/92 VSAT/LSAT- 46/94 Superheat/Subcool- 20/57 Outdoor Entering Air Temp- 82 Outdoor Fan FLA- .60 Compressor RLA/LRA- 5.2/61 Contactor Voltage- 240/24 Capacitor Rating- 35/5 Indoor Return Dry Bulb Temp- 70 Return Wet Bulb Temp- 60 Supply Temp- 54 Temperature Difference- 16 Required Difference- 15-20 Blower FLA- 6.35 Filter Sizes – 16x25x4 Changed Filters – Y customer supplied Blew out drain line: N (no access) Returned tstat to original settings: Y Unit operational; prior to leaving: Y System- Main (2 zones) Approx Age of System: 5 Refrigerant Type- R410a Metering Device- TXV SP/HP: 117/298 SLT/LLT: 60/95 VSAT/LSAT- 39/95 Superheat/Subcool- 21/7 Outdoor Entering Air Temp- 81 Outdoor Fan FLA- .95 Compressor RLA/LRA- 15.40/147 Contactor Voltage- 236/24 Capacitor Rating- 70/7.5 Indoor Return Dry Bulb Temp- 70 Return Wet Bulb Temp-