30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for panorama village, tx


Map of Panorama Village TX
Ronald  E.

Ronald E.


Job Checkin

System- upstairs Approx Age of System: 3 Refrigerant Type- R410a Metering Device- TXV SP/HP: 115/215 SLT/LLT: 56/72 VSAT/LSAT- 38/70 Superheat/Subcool- 18.6/4 Outdoor Entering Air Temp- 70 Outdoor Fan FLA- 1.02 Compressor RLA/LRA- 11.60 Contactor Voltage- 240 Capacitor Rating-30/5 Indoor Return Dry Bulb Temp- 70 Return Wet Bulb Temp- Supply Temp- 56 Temperature Difference- 15-20 Required Difference- Blower FLA- 7.50 Filter Sizes – 20x30x1 (2) Changed Filters – customer stated he recently replaced Blew out drain line: Y System- downstairs Approx Age of System: 2 Refrigerant Type- R410a Metering Device- TXV SP/HP: 121.9/240 SLT/LLT: 58/77 VSAT/LSAT- 40.6/80 Superheat/Subcool- 18.7/4.1 Outdoor Entering Air Temp- 70 O