30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for pinehurst, tx


Map of Pinehurst TX
Jeremy D.

Jeremy D.


Job Checkin

Diagnostic Follow Up Needed Blower motor + Capacitor Pricing New customer has one system total in her one story home. It is approximately 10 years old and currently having problems. She think sit is either not working right because her grand kids keep messing with the thermostat or that there is a leak in their coil that a previous AC guy they use said when he was out last. She says her son noticed there was ice on the coil and there could be a leak. Possibly freezing up too. On arrival called for cool. Humming could be heard from blower motor. Checked furnace. No error codes present. Checked blower motor. Blower motor capacitor is bad rated for 20mfd and operating at 14.44mfd. Blower should be able to turn. Checked voltage to blower motor, 122v. No issue. Checked blower motor bearings and shaft. Blower motor is seized. Recommendations: Comfort Advisor, blower motor, capacitor