System- D/s Approx Age of System: 5 Refrigerant Type- R410a Metering Device- TXV SP/HP: 113.3/359.5 SLT/LLT: 63.2/92.4 VSAT/LSAT- 37.7/108.6 Superheat/Subcool- 25.5/16.2 (Dirty coils) Outdoor Entering Air Temp- 82 Outdoor Fan FLA- 1.1 Compressor RLA/LRA- 12.6/124 (high energy draws on start up) Contactor Voltage- 244.4 Capacitor Rating- 42/7 Indoor Return Dry Bulb Temp- 67.1 Return Wet Bulb Temp- 42.4 Supply Temp- 46.9 Temperature Difference- 20.1 Required Difference- 16-20 Blower FLA- 4.2 Filter Sizes – 20x25x4 Changed Filters – N (Clean filter) Blew out drain line: N (No service valve to blow out drain line) Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- I was approved to replace the insulative material on the refrigerant lines outside before and after pictures were taken and present it to Miss Kim. I went over some concerns regarding the outdoor unit the drain lines and indoor air quality. Scheduled next tune up date: