Job Checkin

AC Diagnostic System: Tiny House Refrigerant Type R410A Metering Device-Fixed Orifice SP/HP 102/317 SLT/LLT 36/97 VSAT/LSAT 32/99 SH/SC 4/2 Outdoor Entering Air Temperature 88 Filter Size(s) 6x24x1 Returned tstat to original settings: Y Unit operational; prior to leaving: Y/N Notes: Upon arrival was shown malfunctioning unit on tiny house on property. They said the unit was not cooling yesterday but they turned it on this morning and it’s cooling. I checked the pressures and found the suction side low. Did not see any obvious refrigerant leaks. Temperature split is 18°, Inside I found the filter grill with no filter in it. I opened the top of the package and found the evaporator coil extremely dirty. Dirty coil could definitely be caused by no filters, and dirty coil can definitely cause low suction pressure and loss of cooling capacity. Recommended an evaporator coil cleaning. Tried to get a hold of property owner and was not able to. Got with Tiffany on site, they have decided