System-main Approx Age of System: 10 Refrigerant Type- R410a Metering Device- TXV SP/HP:155/223 SLT/LLT:54/72 VSAT/LSAT-43/80 Superheat/Subcool-11/8 Outdoor Entering Air Temp-62 Outdoor Fan FLA- 1.7 Compressor RLA/LRA-8.3/52 Contactor Voltage-220/28 Capacitor Rating-45 reading-44.6 Indoor Return Dry Bulb Temp-74 Supply Temp-52 Temperature Difference-22 Required Difference-16-22 Blower FLA- 6.9 Filter Sizes – 20x25x4 Changed Filters –N (clean) Blew out drain line: Y Notes-system is working fine , did recommend air scrubber to eliminate air contaminants . Customer does want to see how this pandemic turns out in order to make any future decisions. Scheduled next tune up date: October 20th 9-11