System: Downstairs Approx Age of System: Combustible Gas Leak Detection Pipe and fittings leak-free: N/A Valves and orifices leak-free: N/A Carbon Monoxide Testing Walk-around CO: pass/ppm 0 Airside CO: pass/return ppm 0 supply ppm 0 Flue gas CO: N/A Ignition and Combustion Delayed ignition: N/A Flame disturbance: N/A Flame discoloration: N/A Motor Amperages and Capacitors Blower motor FLA: 2.4 Induced draft/combustion blower motor FLA: N/A Capacitor(s): fail/mfd 12.8/15 (6%/14.1) Temperature Rise Rated: 20-50 Actual: 31 Static Pressures Blower speed/cfm: RP .21 /SP .12 TESP: Safety Controls Primary limit test: pass Filter sizes: Changed filters: yes or no Scheduled next tune up date: Notes: 20.2 amps at heat strips. Run capacitor is operating below rated value. _______________________________________ System: Upstairs Approx Age of System: Combustible Gas Leak Detection Pipe and fittings leak-free: N/A Valves and orifices leak-free: N/A Carbon Monoxide Testing Walk-a