Job Checkin

System-downstairs Approx Age of System:3 Refrigerant Type- R410a Metering Device- TXV SP/HP:155/229 SLT/LLT:60/81 VSAT/LSAT- 42/88 Superheat/Subcool-18/7 Outdoor Entering Air Temp-73 Outdoor Fan FLA- 1.1 Compressor RLA/LRA-11.6/132.8 Contactor Voltage-28/234 Capacitor Rating-66 of 70 Indoor Return Dry Bulb Temp-75 Supply Temp-56 Temperature Difference-19 Required Difference-16-22 Blower FLA- 8.1 Filter Sizes –20x25x1 Changed Filters –N (clean) Blew out drain line: N (no blow out valve) System-MB Approx Age of System:4 Refrigerant Type- R410a Metering Device- TXV SP/HP:127/218 SLT/LLT:57/80 VSAT/LSAT-45/89 Superheat/Subcool-12/9 Outdoor Entering Air Temp-73 Outdoor Fan FLA- .8 Compress