System- Goodman Approx Age of System: 2 Refrigerant Type-R410a Metering Device- TXV SP/HP:137.3/321.9 SLT/LLT:50.6/90.7 VSAT/LSAT- 47.8/101.1 Superheat/Subcool-2.6/10.1 Outdoor Entering Air Temp-75 Outdoor Fan FLA- .8 Compressor RLA/LRA-9.3/95.6 Contactor Voltage-248.2/26.1 Capacitor Rating-44.72/5.02 Indoor Return Dry Bulb Temp-72.1 Return Wet Bulb Temp-62.6 Supply Temp- 54.8 Temperature Difference-17.3 Required Difference- 16-20 Blower FLA- 3.9 Filter Sizes – 20x25x4 Changed Filters – Y( customer provided) Blew out drain line: y Returned tstat to original settings: Y(75) Unit operational; prior to leaving: Y Notes-Upon arrival, located equipment and made the call for cooling, system kicked on accordingly. Refrigerant pressures are within manufacture specifications for current outdoor temperature. Found compressor was exceeding LRA value on the data plate. Compressor has a strain on it when starting up. Recommend adding compressor saver to the system to aid