30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for shenandoah, tx


Map of Shenandoah TX
Ken P.

Ken P.


Job Checkin

System- 2D Approx Age of System: 16 Refrigerant Type- R22 Metering Device- TXV SP/HP: 63/237 SLT/LLT: 63/106 VSAT/LSAT- 34/111 Superheat/Subcool- 35/10 Outdoor Entering Air Temp- 79 Outdoor Fan FLA- 0.51 Compressor RLA/LRA- 6.4/29 Contactor Voltage- 480 Capacitor Rating- 4.7 of 5 Indoor Return Dry Bulb Temp- 72 Return Wet Bulb Temp- 61 Supply Temp- 56 Temperature Difference- 16 Required Difference- 15-22 Blower FLA- 2.3 Filter Sizes – 20x20x1 Changed Filters – N Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- primary drain pan is corroded and water is passing through into the emergency pan. Changing pan would require pulling the coil which is not recommended on a unit 16 years old. Recommended considering replacement of this unit before water becomes a bigger issue. System- 2E Approx Age of System: 16 Refrigerant Type- R22 Metering Device- TXV SP/HP: 64/218 SLT/LLT: 63/93 VSAT/LSAT- 37/