System- Approx Age of System: 2yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 133/289 SLT/LLT: 56/86 VSAT/LSAT- 46/93 Superheat/Subcool- 46/73 Outdoor Entering Air Temp- 84 Outdoor Fan FLA- 1.0 Compressor RLA/LRA- 12.1/149 Contactor Voltage- 243/25 Capacitor Rating- 68.00/7.33 Indoor Return Dry Bulb Temp- 75 Return Wet Bulb Temp- 59 Supply Temp-57 Temperature Difference- 18 Required Difference- 20-16 Blower FLA- 9.4 Filter Sizes – No Access Changed Filters – No Access Blew out drain line: N (no blowout valve) Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Unit was operational on arrival. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. Condenser LRA is over rating of 134a. Unit has no overflow protection. All other components showed no visible issues at this time. Recommend compressor saver-(to reduce amp and extend equipment life), Overflow protection package-(to protect c