System- upstairs Approx Age of System: 8 Refrigerant Type- R410a Metering Device- TXV SP/HP: 132/300 SLT/LLT: 61/91 VSAT/LSAT- 46/95 Superheat/Subcool- 20/6 Outdoor Entering Air Temp-82 Outdoor Fan FLA- 1.1 Compressor RLA/LRA-10.8/127 Contactor Voltage-240 Capacitor Rating-45/5 actual 45/5 Indoor Return Dry Bulb Temp-72 Return Wet Bulb Temp- 63 Supply Temp- 57 Temperature Difference- 15 Required Difference-15-20 Blower FLA- 7.1 Filter Sizes – 20x25x4 Changed Filters – N Customer will Blew out drain line: N No blow out valve Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Scheduled next tune up date: System- downstairs Approx Age of System: 8 Refrigerant Type- R410a Metering Device- TXV SP/HP: 116/291 SLT/LLT: 62/86 VSAT/LSAT-44/93 Superheat/Subcool-28/7 Outdoor Entering Air Temp-82 Outdoor Fan FLA- 1.3 Compressor RLA/LRA-16.4/144 Contactor Voltage-242 Capacitor Rating-70/10 actual 70/10 Indoor R