System- Upstairs Approx Age of System: 3yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 123/31 SLT/LLT: 57/89 VSAT/LSAT- 41/99 Superheat/Subcool- 15/9 Outdoor Entering Air Temp-90 Outdoor Fan FLA- .9 Compressor RLA/LRA- 10.1/121 Contactor Voltage- 242/25 Capacitor Rating-45/5 Indoor Return Dry Bulb Temp-77 Return Wet Bulb Temp- 60 Supply Temp-59 Temperature Difference- 18 Required Difference- 16-20 Filter Sizes – 20x30x1 Changed Filters – Acceptable Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. All other components showed no visible issues at this time. Recommend compressor saver-(to reduce amp and extend equipment life). System- Downstairs Approx Age of System: 12 Refrigerant Type- R22 Metering Device- TXV SP/HP: 70/193 SLT/LLT: 6403/98 VSAT/L