Follow Up Collect payment System- Master Bedroom Approx Age of System: 4yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 118/361 SLT/LLT: 53/99 VSAT/LSAT- 39/109 Superheat/Subcool-10 Outdoor Entering Air Temp- 97 Outdoor Fan FLA- .5 Compressor RLA/LRA- 6.7/31 Contactor Voltage-240/24 Capacitor Rating-35/5 Indoor Return Dry Bulb Temp- 73 Return Wet Bulb Temp- 57 Supply Temp-50 Temperature Difference- 23 Required Difference- 16-20 Blower FLA- 2.8 Filter Sizes – 20x25x4 Changed Filters – Y (customer supplied) Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. All other components showed no visible issues at this time. Cleaned dehumidifier filter. System- Upstairs Approx Age of System: 4yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 133/379 SLT