30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for spring, tx


Map of Spring TX
Mario S.

Mario S.


Job Checkin

AC Diagnostic System:main Refrigerant Type R410A Metering Device-TXV VSAT/LSAT-47/110 SH/SC-14/8 Outdoor Entering Air Temperature -95 Filter Size(s)20x25x4 Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes: primary line has a restriction causing the inline float switch to trip and cut off the unit. Could add blow out valve and attempt to clear the primary but I strongly Recommend replacement of the system being it is 10 yrs old and a lot of money has been put into it in the past. Robin agreed to have comfort advisor quote new system. Comfort advisor scheduled tomorrow between 9-10. Static’s-RP .05 /FR .52/FS .25 /SP .12TESP: .77