AC Diagnostic System: Main Refrigerant Type R410A Metering Device- TXV SP/HP 67/258 SLT/LLT 83/85 VSAT/LSAT 13/85 SH/SC 69/0.2 Outdoor Entering Air Temperature 83 Notes: Condenser showing low pressure lock out. Reset and found low refrigerant pressures. Checked system with electronic. Leak detector and found major refrigerant leak in the evaporator and a smaller leak at the bottom of the condenser coil. Warranty expires in July 27, 2019. Mr Brehaut would like to relieve a replacement estimate.