AC Diagnostic System: Upstairs Refrigerant Type R22 Metering Device-Fixed Orifice SP/HP 66/236 SLT/LLT 47/95 VSAT/LSAT 38/113 SH/SC 9/18 Outdoor Entering Air Temperature 82 Filter Size(s) 20x25x1 Notes: On arrival blower motor was not operational. Condenser was operational. Checked blower motor electrical. Found faulty capacitor rated for 10mfd operating at 0mfd. Blower motor is dirty. Cooling passages are clogged debris. Wheel is caked. Replaced capacitor. Checked operation. Checked operating temperatures and pressures. Recommendations: Capacitor, blower motor clean (major) Authorizations, payment and permissions were given via phone. . .