Job Checkin

System-main Approx Age of System: 4 years Refrigerant Type- R410a Metering Device- TXV SP/HP: 125/266 SLT/LLT:80/85 VSAT/LSAT-43/88 Superheat/Subcool-37/3 Outdoor Entering Air Temp-75 Outdoor Fan FLA- .8 Compressor RLA/LRA-5.7/76 Contactor Voltage-245/25 Capacitor Rating-42/4.1 of 45/5 Indoor Return Dry Bulb Temp-73 Return Wet Bulb Temp-61 Supply Temp- 50 Temperature Difference-23 Required Difference-16-24 Blower FLA- 4.4 Filter Sizes – 20x25x4 Changed Filters – N clean Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Organic growth spotted in supply plenum, recommend air a scrubber to kill off organic growth, prevent further buildup, as well as increase air quality. Outside unit was wet during temperature and pressure check, temp split shows good refrigerant levels. Scheduled next tune up date: Monday January 4th 8-10